What you need
To connect the server to the PDUs, you need:
Two power cords included with your order
Velcro straps
What you do
To connect the server to the PDUs:
1. Connect a power cord from the left socket in the server to a receptacle in
the PDU on the left side of the rack (based on availability).
2. Use the cable clamp on the server to secure the cable to the server.
3. Connect a power cord from the right socket in the server to a receptacle
in the PDU on the right side of the rack (based on availability).
4. Use the cable clamp on the server to secure the cable to the server.
Step 5: Reassemble the rack
Using Velcro straps and/or cable ties, bundle any excess length of the power
cords and secure them to the rack. Then replace the doors and sides on the
rack.
Chapter 2: Mounting the HCP Anywhere edge appliance into a rack
21