Chapter 8 List of Data Settings
8-6
Monitored data or setting
Change during
RUN operation
Restart after instantaneous power failure or tripping
Selection of restart mode
00 (tripping), 01 (starting with 0 Hz),
02 (starting with matching frequency),
03 (tripping after deceleration and stopping with matching frequency),
04 (restarting with active matching frequency)
Allowable under-voltage power failure
time
Retry wait time before motor restart
Instantaneous power
failure/under-voltage trip alarm enable
00 (disabling), 01 (enabling),
02 (disabling during stopping and decelerating to stop)
Number of restarts on power
failure/under-voltage trip events
00 (16 times), 01 (unlimited)
Input phase loss detection enable
00 (disabling), 01 (enabling)
Restart frequency threshold
0.00 to 99.99, 100.0 to 400.0 (Hz)
Selection of retry after tripping
00 (tripping), 01 (starting with 0 Hz),
02 (starting with matching frequency),
03 (tripping after deceleration and stopping with matching frequency),
04 (restarting with active matching frequency)
Selection of retry after undervoltage
00 (16 times), 01 (unlimited)
Selection of retry count after overvoltage
or overcurrent
Retry wait time after tripping
Electronic thermal function
Electronic thermal setting
0.20 x "rated current" to 1.00 x "rated current" (A)
Electronic thermal setting, 2nd motor
Electronic thermal setting , 3rd motor
Electronic thermal characteristic
00 (reduced-torque characteristic),
01 (constant-torque characteristic),
02 (free setting)
Electronic thermal characteristic, 2nd
motor
Electronic thermal characteristic, 3rd
motor
Free setting, electronic thermal
frequency (1)
Free setting, electronic thermal current
(1)
Free setting, electronic thermal
frequency (2)
Free setting, electronic thermal current
(2)
Free setting, electronic thermal
frequency (3)
Free setting, electronic thermal current
(3)
Overload restriction and overcurrent restraint
Overload restriction operation mode
00 (disabling), 01 (enabling during acceleration and deceleration),
02 (enabling during constant speed), 03 (enabling during acceleration and
deceleration (increasing the speed during regeneration))
Overload restriction setting
0.20 x "rated current" to 2.00 x "rated current" (A)
<0.20 x "rated current" to1.80 x "rated current" (A)> (In case of CT)
0.20 x "rated current" to 1.50 x "rated current" (A)(In case of VT)
Rated current
x 1.50 (CT)
Rated current
x1.20 (VT)
Deceleration rate at overload restriction
Overload restriction operation mode (2)
00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
deceleration (increasing the speed during regeneration))
Overload restriction setting (2)
0.20 x "rated current" to 1.50 x "rated current" (A)
<0.20 x "rated current" to1.50 x "rated current" (A)>
Rated current
x 1.50 (CT)
Rated current
x1.20 (VT)
Deceleration rate at overload restriction (2)
Overcurrent suppression enable
00 (disabling), 01 (enabling)
Active frequency matching, scan start
frequency
0.20 x "rated current" to 2.00 x "rated current" (A)
<0.20 x "rated current" to1.80 x "rated current" (A)> (In case of CT)
0.20 x "rated current" to 1.50 x "rated current" (A) (In case of VT)
Active frequency matching, scan-time
constant
Active frequency matching, restart
frequency select
00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set
frequency)
Software lock mode selection
00 (disabling change of data other than "b031" when SFT is on),
01 (disabling change of data other than "b031" and frequency settings
when SFT is on), 02 (disabling change of data other than "b031"),
03 (disabling change of data other than "b031" and frequency settings),
10 (enabling data changes during operation)
(Note)<>indicate the setting range of 75 to 150kW
(Note) CT : Constant torque mode, VT : Variable torque mode, you can set CT or VT by b049.