Chapter 8 List of Data Settings
8-7
Code
Function name
Monitored data or setting
Default
Memo
Change during
RUN operation
Page
FF
FEF
FUF
b03110
b031=10
Others
b034
Run/power-on warning time
0. to 9999. (0 to 99990), 1000 to 6553 (100000 to 655300) (hr)
0.
Not
Allowed
4-64
b035
Rotational direction restriction
00 (enabling both forward and reverse rotations),
01 (enabling only forward rotation), 02 (enabling only reverse rotation)
00
Not
Not
4-7
b036
Reduced voltage start selection
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage
start time)
6
Not
Allowed
4-42
b037
Function code display restriction
00 (full display), 01 (function-specific display), 02 (user setting),
03 (data comparison display), 04 (basic display)
04
Not
Allowed
4-76
b038
Initial-screen selection
00 (screen displayed when the STR key was pressed last),
001~060 (d001~d060), 201 (F001) 202 *)
01
Not
Allowed
4-78
b039
Automatic user-parameter setting
function enable
00 (disabling), 01 (enabling)
00
Not
Allowed
4-79
Torque limitation
b040
Torque limit selection
00 (quadrant-specific setting), 01 (switching by terminal), 02 (analog input),
03 (option 1), 04 (option 2)
00
Not
Allowed
4-92
b041
Torque limit (1) (forward-driving in
4-quadrant mode)
0. to 200. (%), no (disabling torque limitation)
<0. to 150. (%), no (disabling torque limitation)> (In case of CT)
0. to 150. (%), no (disabling torque limitation)(In case of VT)
150.(CT)
120.(VT)
Not
Allowed
b042
Torque limit (2)
(reverse-regenerating in
4-quadrant mode)
150.(CT)
120.(VT)
Not
Allowed
b043
Torque limit (3) (reverse-driving in
4-quadrant mode)
150.(CT)
120.(VT)
Not
Allowed
b044
Torque limit (4)
(forward-regenerating in
4-quadrant mode)
150.(CT)
120.(VT)
Not
Allowed
b045
Torque limit LADSTOP enable
00 (disabling), 01 (enabling)
00
Not
Allowed
4-94
b046
Reverse Run protection enable
00 (disabling), 01 (enabling)
00
Not
Allowed
4-93
Mode
b049
Dual rating selection
00 (CT : Constant torque)
01 (VT : Variable torque)
00
Not
Not
3-22
Non-stop operation at momentary power failure
b050
Controller deceleration and stop
on power loss
00 (disabling), 01 (nonstop deceleration to stop),
02 (DC voltage constant control, with resume), 03 ( without resume)
00
Not
Not
4-83
b051
DC bus voltage trigger level during
power loss
0.0 to 999.9, 1000. (V)
220.0/440.0
Not
Not
b052
Over-voltage threshold during
power loss
0.0 to 999.9, 1000. (V)
360.0/720.0
Not
Not
b053
Deceleration time setting during
power loss
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
1.00
Not
Not
b054
Initial output frequency decrease
during power loss
0.00 to 10.00 (Hz)
0.00
Not
Not
b055
Proportional gain setting for
nonstop operation at power loss
0.00 to 2.55
0.20
Allowed
Allowed
b056
Integral time setting for nonstop
operation at power loss
0.000 to 9.999 /10.00 to 65.53 (s)
0.100
Allowed
Allowed
Window comparator
b060
Maximum-limit level of window
comparators O
0. to 100. (lower limit : b061 + b062 x 2) (%)
100
Allowed
Allowed
4-71
b061
Minimum-limit level of window
comparators O
0. to 100. (upper limit : b060 - b062 x 2) (%)
0
Allowed
Allowed
b062
Hysteresis width of window
comparators O
0. to 10. (upper limit : b060 - b061 / 2) (%)
0
Allowed
Allowed
b063
Maximum-limit level of window
comparators OI
0. to 100. (lower limit : b064 + b065 x 2) (%)
100
Allowed
Allowed
b064
Minimum-limit level of window
comparators OI
0. to 100. (upper limit : b063 - b065 x 2) (%)
0
Allowed
Allowed
b065
Hysteresis width of window
comparators OI
0. to 10. (upper limit : b063 - b064 / 2) (%)
0
Allowed
Allowed
b066
Maximum-limit level of window
comparators OI
-100. to 100. (lower limit : b067 + b068 x 2) (%)
100
Allowed
Allowed
b067
Minimum-limit level of window
comparators O/OI/O2
-100. to 100. (upper limit : b066 - b068 x 2) (%)
0
Allowed
Allowed
b068
Hysteresis width of window
comparators O/OI/O2
0. to 10. (upper limit : b066 - b067 / 2) (%)
0
Allowed
Allowed
b070
Operation level at O disconnection
0. to 100. (%) or "no" (ignore)
no
Not
Allowed
b071
Operation level at OI disconnection
0. to 100. (%) or "no" (ignore)
no
Not
Allowed
b072
Operation level at O2
disconnection
-100. to 100. (%) or "no" (ignore)
no
Not
Allowed
(Note) <>indicate the setting range of 75 to 150kW
(Note) CT : Constant torque mode, VT : variable torque mode, you can set CT or VT by b049.
*) In case of connecting OPE-S to the inverter, ‘201’ setting is same as ‘00’ setting. Refer to the SJ700D-3 instruction manual.