Chapter 8 List of Data Settings
8-7
Monitored data or setting
Change during
RUN operation
Run/power-on warning time
0. to 9999. (0 to 99990), 1000 to 6553 (100000 to 655300) (hr)
Rotational direction restriction
00 (enabling both forward and reverse rotations),
01 (enabling only forward rotation), 02 (enabling only reverse rotation)
Reduced voltage start selection
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage
start time)
Function code display restriction
00 (full display), 01 (function-specific display), 02 (user setting),
03 (data comparison display), 04 (basic display)
00 (screen displayed when the STR key was pressed last),
001~060 (d001~d060), 201 (F001) 202 *)
Automatic user-parameter setting
function enable
00 (disabling), 01 (enabling)
00 (quadrant-specific setting), 01 (switching by terminal), 02 (analog input),
03 (option 1), 04 (option 2)
Torque limit (1) (forward-driving in
4-quadrant mode)
0. to 200. (%), no (disabling torque limitation)
<0. to 150. (%), no (disabling torque limitation)> (In case of CT)
0. to 150. (%), no (disabling torque limitation)(In case of VT)
Torque limit (2)
(reverse-regenerating in
4-quadrant mode)
Torque limit (3) (reverse-driving in
4-quadrant mode)
Torque limit (4)
(forward-regenerating in
4-quadrant mode)
Torque limit LADSTOP enable
00 (disabling), 01 (enabling)
Reverse Run protection enable
00 (disabling), 01 (enabling)
00 (CT : Constant torque)
01 (VT : Variable torque)
Non-stop operation at momentary power failure
Controller deceleration and stop
on power loss
00 (disabling), 01 (nonstop deceleration to stop),
02 (DC voltage constant control, with resume), 03 ( without resume)
DC bus voltage trigger level during
power loss
Over-voltage threshold during
power loss
Deceleration time setting during
power loss
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
Initial output frequency decrease
during power loss
Proportional gain setting for
nonstop operation at power loss
Integral time setting for nonstop
operation at power loss
0.000 to 9.999 /10.00 to 65.53 (s)
Maximum-limit level of window
comparators O
0. to 100. (lower limit : b061 + b062 x 2) (%)
Minimum-limit level of window
comparators O
0. to 100. (upper limit : b060 - b062 x 2) (%)
Hysteresis width of window
comparators O
0. to 10. (upper limit : b060 - b061 / 2) (%)
Maximum-limit level of window
comparators OI
0. to 100. (lower limit : b064 + b065 x 2) (%)
Minimum-limit level of window
comparators OI
0. to 100. (upper limit : b063 - b065 x 2) (%)
Hysteresis width of window
comparators OI
0. to 10. (upper limit : b063 - b064 / 2) (%)
Maximum-limit level of window
comparators OI
-100. to 100. (lower limit : b067 + b068 x 2) (%)
Minimum-limit level of window
comparators O/OI/O2
-100. to 100. (upper limit : b066 - b068 x 2) (%)
Hysteresis width of window
comparators O/OI/O2
0. to 10. (upper limit : b066 - b067 / 2) (%)
Operation level at O disconnection
0. to 100. (%) or "no" (ignore)
Operation level at OI disconnection
0. to 100. (%) or "no" (ignore)
Operation level at O2
disconnection
-100. to 100. (%) or "no" (ignore)
(Note) <>indicate the setting range of 75 to 150kW
(Note) CT : Constant torque mode, VT : variable torque mode, you can set CT or VT by b049.
*) In case of connecting OPE-S to the inverter, ‘201’ setting is same as ‘00’ setting. Refer to the SJ700D-3 instruction manual.