Chapter 8 List of Data Settings
8-8
Monitored data or setting
Change during
RUN operation
Cumulative input power data clearance
Clearance by setting "01" and pressing the STR key
Cumulative input power display gain
setting
Start frequency adjustment
Carrier frequency setting
0.5~15.0(kHz) <0.5~10.0(kHz)> (In case of CT)
0.5~12.0(kHz) (In case of VT)
Initialization mode (parameters or trip
history)
00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)
Country code for initialization
00 (Japan), 01 (EU), 02 (U.S.A.)
Frequency scaling conversion factor
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (starting with active matching frequency)
Automatic carrier frequency reduction
Dynamic braking usage ratio
00 (deceleration until stop), 01 (free-run stop)
00 (always operating the fan), 01 (operating the fan only during
inverter operation [including 5 minutes after power-on and
power-off])
00 (disabling), 01 (enabling [disabling while the motor is topped]),
02 (enabling [enabling also while the motor is topped])
Dynamic braking activation level
330 to 380, 660 to 760(V)
Thermistor for thermal protection
control
00 (disabling the thermistor), 01 (enabling the thermistor with PTC),
02 (enabling the thermistor with NTC)
Thermal protection level setting
Free setting of V/f characteristic
Free-setting V/f frequency (1)
0. to "free-setting V/f frequency (2)" (Hz)
Free-setting V/f voltage (1)
Free-setting V/f frequency (2)
"free-setting V/f frequency (1)" to "free-setting V/f frequency (3)" (Hz)
Free-setting V/f voltage (2)
Free-setting V/f frequency (3)
"free-setting V/f frequency (2)" to "free-setting V/f frequency (4)" (Hz)
Free-setting V/f voltage (3)
Free-setting V/f frequency (4)
"free-setting V/f frequency (3)" to "free-setting V/f frequency (5)" (Hz)
Free-setting V/f voltage (4)
Free-setting V/f frequency (5)
"free-setting V/f frequency (4)" to "free-setting V/f frequency (6)" (Hz)
Free-setting V/f voltage (5)
Free-setting V/f frequency (6)
"free-setting V/f frequency (5)" to "free-setting V/f frequency (7)" (Hz)
Free-setting V/f voltage (6)
Free-setting V/f frequency (7)
"free-setting V/f frequency (6)" (Hz) to 400. (Hz)
Free-setting V/f voltage (7)
00 (disabling), 01 (enabling)
Brake Wait Time for Release
Brake Wait Time for Acceleration
Brake Wait Time for Stopping
Brake Wait Time for Confirmation
Brake Release Frequency Setting
0.00 to 99.99, 100.0 to 400.0 (Hz)
Brake Release Current Setting
0.0 to 2.00 x "rated current" <0.0 to 1.80 x "rated current">
0.00 to 99.99, 100.0 to 400.0 (Hz)
Overvoltage suppression enable
00 (disabling the restraint), 01 (controlled deceleration),
02 (enabling acceleration),. 03 (enabling acceleration)
Overvoltage suppression level
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
Acceleration and deceleration rate at
overvoltage suppression
Overvoltage suppression propotional
gain
Overvoltage suppression Integral time
0.000 to 9.999 / 10.00 to 65.53 (s)
Output loss detection enable
00 (disabling), 01 (enabling)
Output loss detection sensibility
Automatic return to initial display
00 (disabling), 01 (enabling)
00 (Read/Write OK), 01 (Protected)
00 (Initialization disable), 01 (Perform initialization)
(Note)<>indicate the setting range of 75 to 150kW