Chapter 8 List of Data Settings
8-12
Code
Function name
Monitored data or setting
Default
Memo
Change during
RUN operation
Page
FF
FEF
FUF
b03110
b031=10
Terminal
C111
Overload setting (2)
0.20 to 2.00 x "rated current" (A)
<0.20 to 1.80 x "rated current" (A) > (In case of CT)
0.20 to 1.50 x "rated current" (A) (In case of VT)
Rated current
Allowed
Allowed
4-40
Adjustment
C121
[O] input zero calibration
0. to 9999., 1000 to 6553 (10000 to 65530)
Factory setting
Allowed
Allowed
-
C122
[OI] input zero calibration
Factory setting
Allowed
Allowed
C123
[O2] input zero calibration
Factory setting
Allowed
Allowed
Output terminal operation function
C130
Output 11 on-delay time
0.0 to 100.0 (s)
0.0
Not
Allowed
4-72
C131
Output 11 off-delay time
0.0
Not
Allowed
C132
Output 12 on-delay time
0.0 to 100.0 (s)
0.0
Not
Allowed
C133
Output 12 off-delay time
0.0
Not
Allowed
C134
Output 13 on-delay time
0.0 to 100.0 (s)
0.0
Not
Allowed
C135
Output 13 off-delay time
0.0
Not
Allowed
C136
Output 14 on-delay time
0.0 to 100.0 (s)
0.0
Not
Allowed
C137
Output 14 off-delay time
0.0
Not
Allowed
C138
Output 15 on-delay time
0.0 to 100.0 (s)
0.0
Not
Allowed
C139
Output 15 off-delay time
0.0
Not
Allowed
C140
Output RY on-delay time
0.0 to 100.0 (s)
0.0
Not
Allowed
C141
Output RY off-delay time
0.0
Not
Allowed
C142
Logical output signal 1 selection 1
Same as the settings of C021 to C026 (except those of
LOG1 to LOG6)
00
Not
Allowed
C143
Logical output signal 1 selection 2
00
Not
Allowed
C144
Logical output signal 1 operator selection
00 (AND), 01 (OR), 02 (XOR)
00
Not
Allowed
4-66
C145
Logical output signal 2 selection 1
Same as the settings of C021 to C026 (except those of
LOG1 to LOG6)
00
Not
Allowed
C146
Logical output signal 2 selection 2
00
Not
Allowed
C147
Logical output signal 2 operator selection
00 (AND), 01 (OR), 02 (XOR)
00
Not
Allowed
C148
Logical output signal 3 selection 1
Same as the settings of C021 to C026 (except those of
LOG1 to LOG6)
00
Not
Allowed
C149
Logical output signal 3 selection 2
00
Not
Allowed
C150
Logical output signal 3 operator selection
00 (AND), 01 (OR), 02 (XOR)
00
Not
Allowed
C151
Logical output signal 4 selection 1
Same as the settings of C021 to C026 (except those of
LOG1 to LOG6)
00
Not
Allowed
C152
Logical output signal 4 selection 2
00
Not
Allowed
C153
Logical output signal 4 operator selection
00 (AND), 01 (OR), 02 (XOR)
00
Not
Allowed
C154
Logical output signal 5 selection 1
Same as the settings of C021 to C026 (except those of
LOG1 to LOG6)
00
Not
Allowed
C155
Logical output signal 5 selection 2
00
Not
Allowed
C156
Logical output signal 5 operator selection
00 (AND), 01 (OR), 02 (XOR)
00
Not
Allowed
C157
Logical output signal 6 selection 1
Same as the settings of C021 to C026 (except those of
LOG1 to LOG6)
00
Not
Allowed
C158
Logical output signal 6 selection 2
00
Not
Allowed
C159
Logical output signal 6 operator selection
00 (AND), 01 (OR), 02 (XOR)
00
Not
Allowed
Input terminal response
C160
Input terminal response time setting 1
0. to 200. ( 2ms)
1
Not
Allowed
4-72
C161
Input terminal response time setting 2
0. to 200. ( 2ms)
1
Not
Allowed
C162
Input terminal response time setting 3
0. to 200. ( 2ms)
1
Not
Allowed
C163
Input terminal response time setting 4
0. to 200. ( 2ms)
1
Not
Allowed
C164
Input terminal response time setting 5
0. to 200. ( 2ms)
1
Not
Allowed
C165
Input terminal response time setting 6
0. to 200. ( 2ms)
1
Not
Allowed
C166
Input terminal response time setting 7
0. to 200. ( 2ms)
1
Not
Allowed
C167
Input terminal response time setting 8
0. to 200. ( 2ms)
1
Not
Allowed
C168
Input terminal response time setting FW
0. to 200. ( 2ms)
1
Not
Allowed
Other
C169
Multistage speed/position determination time
0. to 200. ( 10ms)
0
Not
Allowed
4-48
4-108
(Note)<>indicate the setting range of 75 to 150kW