- Note that there are diffrence of setting range and defaults between CT mode and VT mode.
- Note that you change 00 to 01 with the parameter b049, initial data are renewed to below VT mode data.
V/F characteristic curve
selection, 1st motor
00 (VC), 01 (VP), 02 (free V/f),
03 (sensorless vector control),
04 (0Hz sensorless vector control),
05(vector with sensor)
00 (VC), 01 (VP), 02 (free V/f),
03 (sensorless vector control),
V/F characteristic curve
selection, 2nd motor
00 (VC), 01 (VP), 02 (free V/f),
03 (sensorless vector control),
04 (0Hz sensorless vector control),
05(vector with sensor)
00 (VC), 01 (VP), 02 (free V/f),
03 (sensorless vector control),
DC braking force during
deceleration
0. to 100.(%)
<0. to 80.(%)>
0. to 70.(%)
< 0. to 50.(%) >
DC braking force for
starting
0. to 100.(%)
<0. to 80.(%)>
0. to 70.(%)
<0. to 50.(%)>
DC braking carrier
frequency setting
0.5 to 15.0(kHz)
<0.5 to 10.0(kHz)>
0.5 to 12.0(kHz)
<0.5 to 8.0(kHz)>
00 (normal operation),
01 (energy-saving operation)
02 (fuzzy operation)
00 (normal operation),
01 (energy-saving operation)
Overload restriction
setting
0.20 to 2.00 x Rated current(A)
<0.20 to 1.80 x Rated current(A)>
0.20 to 1.50 x Rated current(A)
Overload restriction
setting (2)
Active frequency
matching, scan start
frequency
0.20 to 2.00 x Rated current(A)
<0.20 to 1.80 x Rated current(A)>
0.20 to 1.50 x Rated current(A)
Torque limit (1)
(forward-driving in
4-quadrant mode)
0. to 200.(%)/ __no
<0. to 180.(%)/ __no>
Torque limit (2)
(reverse-regenerating
in 4-quadrant mode)
Torque limit (3)
(reverse-driving in
4-quadrant mode)
Torque limit (4)
(forward-regenerating
in 4-quadrant mode)
Note: < > indicate the setting range of 75 to 150kW