3-24
Carrier frequency
setting
0.5 to 15.0(kHz)
<0.5 to 10.0(kHz)>
0.5 to 12.0(kHz)
<0.5 to 8.0(kHz)>
00 (disabling), 01 (enabling)
Digital current monitor
reference value
0.20 x Rated current to 1.50 x
Rated current (A)
(Current with digital current
monitor output at 1,440 Hz)
0.00 to 1.50 x Rated current
(A)
Low-current indication
signal detection level
0.00 to 2.00 x rated current(A)
<0.00 to 1.80 x Rated current(A)>
0.00 to 1.50 x Rated current
(A)
0.00 to 2.00 x rated current (A)
<0.00 to 1.80 x Rated current(A)>
0.00 to 1.50 x Rated current
(A)
Over-torque
(forward-driving) level
setting
0. to 200.(%)
<0. to 180.(%)>
Over-torque (reverse
regenerating) level
setting
Over-torque (reverse
driving) level setting
Over-torque (forward
regenerating) level
setting
0.00 to 2.00 x rated current
<0.00 to 1.80 x Rated current(A)>
0.00 to 1.50 x Rated current
(A)
Note: < > indicate the setting range of 75 to 150kW