Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 123
May 2019
Pulse/Frequency/Quadrature Module Wiring (Figure 73 through Figure 79)
The 4 Channel Pulse/Frequency/Quadrature Module provides four different functionalities in the form of
Pulse Input, Frequency measurement, Quadrature encoder input and Pulse Output. Each of the 4 channels
can be configured for any one of these four functionalities; with the exception that quadrature encoder
input (A and B pulses) can be applied to only Channels 1 and 2 respectively. When configured for
quadrature, Channels 3 and 4 will still be available for use.
The Pulse Output functionality uses the digital output available on the module for outputting pulses.
Before installing be sure to set the module DIP switches for differential or single ended. See page 90.
Figure 73 Pulse Counting Wiring