204 ControlEdge HC900 Process & Safety Controller User and Installation Manual Revision 10
May 2019
1. Remove the module and
check for a bent pin, then
reinsert the module
2. Measure power supply
voltage. If not correct, replace
power supply.
3. Replace module
4. Replace rack
CRC failure of primary
and backup factory
calibration
CRC failure of field
calibration values
1. Remove/reinsert module.
2. Replace module.
General Hardware
Failure (AI=convertor
not working)
The software residing
on the module does
not match the module
type. This diagnostic
should only result in
the factory.
The loopback test of
the shift register failed.
Bad I/O Channel Diagnostics
Individual channels on I/O modules indicate their diagnostics by 6 flashes on the Scanner and CPU; the
channel’s LED does not indicate a diagnostic. Table 34 is a list of conditions that can cause a bad channel
diagnostic.
Table 34 – Bad I/O Channel Diagnostics
Failure message
indicated on Honeywell
OI or Honeywell
HCDesigner/Utilities
function block monitor
The sensor – T/C, RTD, or mV source -- is
failing burnout checks.
Check terminal block
connections
Replace source element
Replace module.
The signal at the terminals is less than
10% below the range of the sensor.
Check the signal level being
applied to the terminals.
Replace module.
The signal at the terminals is more than
10% over the range of the sensor.
Check the signal level being
applied to the terminals.
Replace module.