Failure message
indicated on Honeywell
OI or Honeywell
HCDesigner/Utilities
function block monitor
When attempting to take a reading, the
ADC fails. This could result if the incoming
signal is either too large or small. It also
could result if the ADC circuit is failing. If
the problem is the ADC circuit, most likely
other channels will have the same failure.
Check the signal level being
applied to the terminals.
Replace module.
The board indicates that the channel is
failing to output the correct value.
Check terminal connections.
Replace module.
The number of configured channels in the
DO function block exceeds the number of
hardware channels on the DO card.
Reconfigure the DO function
block.
Replace DO card with correct
number of channels.
Either field wire is open or channel HW is
open
Either field wire is shorted or channel HW
inside module is shorted
IO module is not able to drive output
1. Check load is within
supported range
2. Check field wiring
3. Restart module
4. Replace module
AI/DI voting failing within module
1. Restart module
2. Replace module
External field supply failure
Field supply voting is not within supported
range
1. Check the field supply
voltage
2. Check field supply wiring
ECxx where xx is a number
IO module detected internal HW fault
during self-diagnostics
1. Restart module
2. Replace module