Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 203
May 2019
I/O Module Diagnostic Indication
To indicate the type of diagnostic failure, the module’s status LED is flashed red with a number of quick
strobes followed by a long off time. Table 33 outlines the potential module diagnostics.
Hazardous voltages exist at terminal blocks.
AO8 and AO16 modules require at least one channel to be configured prior to a cold start for the module
to work properly. Subsequent channels then may be added with a hot start.
Failure to comply with these instructions could result in death or serious injury.
Table 33 I/O Module LED Diagnostics
Number
of
Strobes
Failure
Description
UIO
AI
AO
DI
DO
PFQ
User Action
Contact
AC
DC
Relay
AC
DC
1
FAIL SAFE
The module is in the
failsafe state because it
is not receiving
message requests
from the CPU or
Scanner at a rate that
satisfies the configured
failsafe timeout.
Gas
Analyzer
1. If expansion I/O rack, go to
step 2. If no expansion I/O
rack, go to step 3.
2. Check the Scanner status
LED (see p. 191).
If its flashing 6 times,
proceed with step 3.
If its flashing some other
red status code, refer to
Table 31 to solve that
problem first.
If its flashing green, the
module probably is not
required in the configuration.
If its not on or steady, cycle
power to the scanner.
3. Make sure the module is the
correct one for the
configuration.
4. Remove the module and
check for a bent pin, then
reinsert the module
5. Replace the module
6. Remove other modules and
replace one at a time until the
problem reoccurs. Most likely
the last module inserted
needs to be replaced.
7. Replace the rack.
2
EAROM
EA ROM Failed its
checksum
1. Remove/reinsert module.
2. Replace module.
3
RAM
Field faults
Field power supply
failures, Line monitor
faults
1. Repair field power
supply/connection
2. Repair field wiring
3. Replace module
4
ROM
1. Remove/reinsert module.
2. Replace module.