134 ControlEdge HC900 Process & Safety Controller User and Installation Manual Revision 10
May 2019
Figure 84 - Field wiring for analog output
Field wiring for Digital Input (Dry Contact)
A UIO channel configured as a Digital Input. See the following table for DI specification:
Parameter
Specification
Open Voltage
24V
Short Circuit Current
7 mA
Open Contact
15 kΩ > 0.1 W
A
Closed Contact
5 kΩ > 0.25 W
B
Short circuit detection:
I > 6mA +/-5%
Closed contact detection:
2.8mA < I < 6mA +/-5%
Lead Breakage Detection
I < 0.9mA +/-5%
Input filter
First-order low-pass 1kHz
Note A: At 24 VDC, equates to 8.57 KΩ > R > 4 KΩ (where R = total loop resistance)
Note B: At 24 VDC, equates to 26.7 KΩ > R > 10 KΩ