Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 151
May 2019
Step
Action
8
Key in the following command string:
AT Y0
Then, press the ENTER key.
The modem should respond with OK.
9
Key in the following command string:
AT &B1
Then, press the ENTER key.
The modem should respond with OK.
10
Key-in the following command string:
AT E0 Q1 &W0
The Modem will not respond.
11
Power down the modem and disconnect it from the PC.
12
Set the modem switches to the following:
Switch
Setting
Position
Function
1
ON
DOWN
Modem ignores DTR (Override)
2
OFF
UP
Verbal (word) results
3
OFF
UP
Suppresses result codes
4
ON
DOWN
Suppresses echo
5
OFF
UP
Modem answers on first ring
6
ON
DOWN
CD always ON (Override)
7
OFF
UP
Loads Y0-Y4 configuration from user-defined
nonvolatile memory (NVRAM)
8
OFF
UP
Disables command recognition (dumb mode)
13
Connect the modem to the 25 pin cable connector.
14
Connect the modem to a telephone jack.
15
Power up the modem and the ControlEdge HC900 Controller.
16
On a remote computer, run Designer Software.
17
Set up Designer Software to dial the ControlEdge HC900 Controller.
18
Verify that communications are established with the remote ControlEdge HC900 Controller.