An AI module’s CJ
temperature reading is
indicating a thermal problem.
The scanner determines this
problem not the AI module;
therefore, the module’s status
LED will not indicate this
diagnostic.
Possible reasons for this
diagnostic are:
1. One of the two CJs on the
module is indicating a
temperature reading greater
than 70 degrees C.
2. Both cold-junction sensors
are failing to convert.
3. The CJs are converting
properly, but their
differential is greater than
10 degrees C.
1. Improve ventilation to rack
2. Replace AI module
The scanner determined that a
module has a bad channel. In
this condition, the module’s
status LED will not indicate the
failure because the Scanner
determines the condition, not
the module itself.
Refer to the Bad I/O Channel
Diagnostics on page 197 to
determine the nature of the
problem and possible user
actions.
One of the power-supplies
failed.