Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 233
May 2019
Analog Input accuracy specification
Range
AI Module Accuracy
RTP + Cable Accuracy
AI Module + RTP
Accuracy
100 Plat. RTD
0.1% of Range
0.04% Range (0.357C)
0.14% of Range
JIS RTD
0.1% of Range
0.12% Range (0.824C)
0.22% of Range
10 Cu. RTD
0.1% of Range
0.57% Range (1.540C)
0.67% of Range
200 OHMS
0.1% of Range
0.07% Range (0.140)
0.17% of Range
0-10mV LINEAR
0.1% of Range
0.04% Range (0.004mV)
0.14% of Range