Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 51
May 2019
Calculate 5V current
( D = A * B )
Calculate 24V current
( E = A * C )
Controller (C30 and C30S)
820 mA
legacy.
1100 mA
New.
Controller (C50 and C50S)
930 mA
legacy.
1100 mA
New.
Controller (C70 and C70S)
1150mA
legacy.
1350 mA
New.
1500 mA
legacy.
1500 mA
New.
Scanner 1 Port (S50/S50S)
670 mA
legacy.
750 mA
New.
Scanner 2 Port (S75/S75S)
770 mA ,
legacy.
950 mA
New.
Power Status Module (PSM)
AC Digital Input (16 pts)
DC Digital Input (16 pts)
AC/DC Digital Input (16 pts)
DC Digital Input (32 pts)
AC Digital Output (8 pts)
DC Digital Output (16 pts)
DC Digital Output (32 pts)
Pulse/Frequency/Quadrature**
Safety Universal Input Output
(16 pts)
*Limit 10, 4 channel Analog Output modules per I/O rack.
** Limit 4 PFQ modules per I/O rack.