Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 51
May 2019
A
B
C
D
E
Module type
Enter
Quantity
Max
Current @
5 V
Max
Current @
24 V
Calculate 5V current
( D = A * B )
Calculate 24V current
( E = A * C )
Controller (C30 and C30S)
( )
820 mA
legacy.
1100 mA
New.
0 mA
( )
( 0 )
Controller (C50 and C50S)
( )
930 mA
legacy.
1100 mA
New.
0 mA
( )
( 0 )
Controller (C70 and C70S)
( )
1150mA
legacy.
1350 mA
New.
0 mA
( )
( 0 )
Controller (C75/ C75S)
( )
1500 mA
legacy.
1500 mA
New.
0 mA
( )
( 0 )
Scanner 1 Port (S50/S50S)
( )
670 mA
legacy.
750 mA
New.
0 mA
( )
( 0 )
Scanner 2 Port (S75/S75S)
( )
770 mA ,
legacy.
950 mA
New.
0 mA
( )
( 0 )
Power Status Module (PSM)
( )
22 mA
0 mA
( )
( 0 )
Analog Input (8 pts)
( )
40 mA
25 mA
( )
( )
Analog Input (16 pts)
( )
75 mA
50 mA
( )
( )
Analog Output (4 pts)*
( )
40 mA
200 mA
( )
( )
Analog Output (8 pts)
( )
225 mA
350 mA
( )
( )
Analog Output (16 pts)
( )
350 mA
700 mA
( )
( )
AC Digital Input (16 pts)
( )
130 mA
0 mA
( )
( 0 )
DC Digital Input (16 pts)
( )
130 mA
0 mA
( )
( 0 )
AC/DC Digital Input (16 pts)
( )
130 mA
0 mA
( )
( 0 )
Contact Input (16 pts)
( )
130 mA
40 mA
( )
( )
DC Digital Input (32 pts)
( )
215 mA
0 mA
( )
( 0 )
AC Digital Output (8 pts)
( )
220 mA
0 mA
( )
( 0 )
DC Digital Output (16 pts)
( )
340 mA
0 mA
( )
( 0 )
DC Digital Output (32 pts)
( )
235 mA
0 mA
( )
( 0 )
Relay Output (8 pts)
( )
110 mA
100 mA
( )
( )
Pulse/Frequency/Quadrature**
( )
110 mA
250 mA
( )
( )
Safety Universal Input Output
(16 pts)
( )
10 mA
100 mA
( )
( )
*Limit 10, 4 channel Analog Output modules per I/O rack.
** Limit 4 PFQ modules per I/O rack.
Total mA @ 5V =
( )
Total mA @ 24V=
( )

Table of Contents