AQ252 Universal Injection/Mixing Boiler Reset Control Panels
37 69-1986—02
A/C EQUIP CONFIG Central A/C – Available only if no AQ158 controller is present on the network.
ZONE A-1 to D-16 A-1 Selects the desired zone.
A/C UNIT NONE / 1 1 Defines which A/C compressor is associated with each
zone thermostat.
NOTE: At this time, only one zone of A/C can be handled
by the AQ2000 controls. The options are 1 (if the
zone uses an AQ1000TP2 programmable
thermostat and can call for cooling), or NONE.
COOLING ENABLE / DISABLE ENABLE Enables or disables the cooling functions of the zone's
programmable thermostat (AQ1000TP2).
NOTE: This item is always set to DISABLE when a non-
programmable thermostat (AQ1000TN2) is used
in the selected zone.
STATISTICS Displays the summary and Zone relay activity (hours of operation or cycles since last reset)
LAST DATA
RESET
Max. 24,855 days (68 years) 2000 JAN 01 Date of last reset formatted as YYYY MMM DD.
RESET ALL DATA
ARE YOU SURE?
YES / NO NO Selecting YES resets all of the summary and zone activity
values to zero.
BOILER FIRE
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
BOILER PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
DHW PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
AUX PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
SEC PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
INJ PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
AUX OUT
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
MIX VLV. OPEN
CYCLE
Maximum of 10,000,000
cycles
0 Displays number of valve open cycles since last reset.
MIX VLV. CLOSE
CYCLE
Maximum of 10,000,000
cycles
0 Displays number of valve close cycles since last reset.
ZONE A-1
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the zone's relay (e.g., zone A-1)
since last reset.
The zone Identifier is A-1 through D-16.
ENVIRACOM Not used - reserved for future use.
Modules ID: n/a n/a n/a
Table 6. Installer Menu – Equipment Setup. (Continued)
EQUIPMENT SETUP
Menu Option Range
Factory
Default Description