EasyManuals Logo

Honeywell AQ25A Series User Manual

Honeywell AQ25A Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #169 background imageLoading...
Page #169 background image
AQ25400B “ADD-A-TEMPERATURE” EXPANSION CONTROL PANEL
17 69-1987—02
TEST (continued)
SENSOR Tests the secondary mixed loop temperature sensor to ensure correct operation
SEC - -
LO
-49° to 257°F (-45° to 125°C)
HI
n/a Displays the temperature measured by the secondary
mixed water sensor.
“- -” means sensor is disconnected
LO means temperature reading is below -49°F (-
45°C)
HI means temperature reading is above 257°F
(125°C)
EXIT n/a n/a Exits this sub-menu and returns to the Installer menu.
ZONES Tests the zone equipment individually, or sequentially, to ensure correct operation
ALL n/a OFF Sequentially energizes / de-energizes all zones
connected to the AQ254 group of zones.
0 displays when the AQ254 Control Module has
confirmation that the zone’s pump is de-energized
or its valve is fully closed.
1 displays when the AQ254 Control Module has
confirmation that the zone’s pump is energized or
its valve is fully open.
In the case of pump zoning, the 1 displays no more
than 5 seconds after the activation of the relay. In the
case of valve zoning, the 1 displays either when the
zone valve operating time (defined in EQUIPMENT
SETUP > ZONING > ZONE VALVES TIME TO OPEN
on the main AQ2000 Series Control Panel) has
elapsed (AQ1554P2) or when the valve’s end switch
is closed (AQ1574V4).
ZONE B-1 0/1
ZONE B-16 0/1
0/1 0 Energizes / de-energizes each zone individually.
0 displays when the AQ254 Control Module has
confirmation that the zone’s pump is de-energized
or its valve is fully closed.
1 displays when the AQ254 Control Module has
confirmation that the zone’s pump is energized or
its valve is fully open.
EXIT n/a n/a Exits this sub-menu and returns to the Installer menu.
PURGE Purges all (or individual) zones for the period of time selected in the PURGE TIME menu
option
PURGE TIME 1 to 30
(minutes)
5:00
(minutes)
Duration of purge for each zone selected.
PURGE PURG ALL / DHW /
PURGE 1 … PURGE 16
ALL Installer selects which zones to purge (all, only DHW,
or individual zones).
START PURGE START PURGE /
STOP PURGE
n/a Starts and Stops purge operation.
PURGE OFF WAIT VALVE /
PURGE COMPLETE
n/a Indicates status of the system during a Purge
operation.
Displays only if START PURGE is active.
EXIT n/a n/a Exits this sub-menu and returns to the Installer menu.
Table 3. Installer Menu. (Continued)
EQUIPMENT SETUP
Menu Option Range
Factory
Default Description

Table of Contents

Other manuals for Honeywell AQ25A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AQ25A Series and is the answer not in the manual?

Honeywell AQ25A Series Specifications

General IconGeneral
BrandHoneywell
ModelAQ25A Series
CategoryControl Panel
LanguageEnglish

Related product manuals