EasyManuals Logo

Honeywell AQ25A Series User Manual

Honeywell AQ25A Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
33 69-2119—02
AUXILIARY I/O
Settings which the AQ25A uses to control the system based on input to the AUX. IN terminals or
to control the activation of the AUX.OUT and AUX.PUMP outputs.
AUX.IN
(optional)
SETBACK / VACANCY /
EM. SHUT / NONE
SETBACK Based on the setting chosen, the AQ25A sets the system
in one of 3 different levels of setback for as long as the
Aux. In terminals are shorted. Refer to instruction sheet for
AQ1000 thermostat (69- 2005EF) for setting the Vacancy
(Freeze Protection) temperature setpoint.
AUX.OUT
(optional)
BOILER / SETBACK /
ZONE OP. / ALARM /
AUX.IN / DHW IN / HEAT IN /
HT DMND / COOL / NONE
BOILER Based on the setting chosen, the AQ25A closes the AUX.
Out dry contact terminals when:
BOILER: The boiler pump energizes.
SETBACK: The system program is in setback mode
(either SLEEP or LEAVE).
ZONE OP.: The end switch of a zone valve connected
to a Zoning Module closes or a zone pump energizes.
ALARM: An alarm is detected on the system.
AUX.IN, DHW IN, HEAT IN, or HEAT DMND: An input
signal is detected on the respective terminals.
COOL: There is a call for cooling from a programmable
AQ1000 thermostat. The COOL option is available only
if central A/C is present; see the “A/C SETTINGS” and
“A/C EQUIP CONFIG” menu options in this table.
NONE: indicates that the Aux Out terminals are not
used.
AUX.PUMP
(optional)
BOILER / GROUP / OCC /
BYPASS / FAN / NONE /
AUX.IN / DHW IN / HEAT IN /
HT DMND
BOILER Based on the setting chosen, the AQ25A closes the Aux.
Pump dry contacts when:
BOILER: The boiler pump energizes.
GROUP: Any of the thermostats in a Group of zones
(identified by the Zoning Module's DIP switch #7 [AUX]
being switched to YES) energize.
OCC: The system program is in Occupied mode (either
WAKE or RETRN).
BYPASS: The boiler return sensor measures a water
temperature less than the value defined for the
EQUIPMENT SETUP > BOILER SETTING > MIN
RETURN setting.
FAN: There is a call for cooling from a programmable
AQ1000 thermostat. The FAN option is available only
if
central A/C is present; see the “A/C SETTINGS” and
“A/C EQUIP CONFIG” menu options in this table
AUX.IN, DHW IN, HEAT IN, or HEAT DMND: An input
signal is detected on the respective terminals.
NONE: indicates that the Aux Pump terminals are not
used.
A/C SETTINGS Central A/C – Available only if no AQ158 controller is present on the network.
CYCLES/HOUR 2 / 3 / 4 / 5 / 6 4 The maximum number of times the controller will permit
the central A/C to cycle in each hour.
MIN.OFF TIME 2 to 10 (minutes) 5M The length of time that must elapse after the AC
compressor shuts off before the Aux. Out relay is permitted
to close, to energize the compressor again.
C.W.S.D. - -
32°F to 100°F (0°C to 38°C)
65°F
(18°C)
The temperature at which cold weather shutdown is
activated.
“- -” means Off (not used).
FAN MODE AUTO / ON AUTO Selects whether or not the fan serving the A/C system
operates constantly (ON) or operates only when there is a
call for cooling (AUTO).
FAN MODE displays only if the FAN option is selected for
AUX.PUMP. See “AUX.PUMP” menu option in this table.
Table 6. Installer Menu – Equipment Setup. (Continued)
EQUIPMENT SETUP
Menu Option Range
Factory
Default Description

Table of Contents

Other manuals for Honeywell AQ25A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AQ25A Series and is the answer not in the manual?

Honeywell AQ25A Series Specifications

General IconGeneral
BrandHoneywell
ModelAQ25A Series
CategoryControl Panel
LanguageEnglish

Related product manuals