WEBs CIPer Model 50 – USER GUIDE 
 
 11    31-00198—01   
 
Adjusting alarm poll-rate for the HMI 
The update rate for alarms and data-points on the HMI has a default setting. 
This can be adjusted with the CPU performance, to balance the information demand. 
 
IMPORTANT: 
I) The faster the alarm and data-point poll rate, the more impact it will have on the performance of 
the station. This might slower the CPU or station performance. 
II) Default setting for alarm and data-point poll-rate is 15s (15.000 millisecond). 
III) Adjustable range is from 5s to 120s (5.000…120.000 millisecond). 
IV) By default, the poll-rate setting is hidden and can be made visible in the Slot Sheet. 
When adjusting for faster polling, watch the CPU load of the station. 
 
To change the alarm poll rate, select the alarm menu item and select the Slot Sheet: 
 
 
Right click the “updateIntervalMillis” and uncheck the “Hidden” flag.