WEBs CIPer MODEL 50 – USER GUIDE 
31-00198—01    4 
Order numbers (SKU) 
The onboard HMI is featured in the below listed order numbers: 
•  WEB-EAGLENX26D 
•  WEB-EAGLENX26ND 
 
IMPORTANT: 
To make efficient use of HMI functionality, it is required to do a few set-up steps in Honeywell WEBStation 
N4.4.93.40.8 or higher. Refer section “HMI configuration principles” given below. 
 
•  WEB-EAGLENX26D 
 
The XL2000HMI can be connected and operated with the below listed OS (SKU) numbers. 
 
•  WEB-EAGLENX26ND 
 
 
 
 
 
 
 
HMI configuration principles 
To get the onboard HMI or detached HMI operational, the following configuration principles need to be done 
in WEBs N4: 
 
1.  Add & enable the HMI Service. 
2.  Set the PIN for the HMI access. 
3.  Add HMI and LED Alarm recipients. 
 
NOTE:    As  long  as  there  are  un-acknowledged  alarms  in  the  station,  the  alarm  symbol  will  be  blinking, 
regardless if a user is logged-in to the HMI or not. See below picture: 
 
 
 
 
 
 
 
4.  Configure the alarming for the HMI. 
5.  Fill the Fast Access Lists (FAL) with data-points, schedules & parameters. 
6.  If desired, create a custom HMI sequence.