WEBs CIPer Model 50 USER GUIDE
25 31-0019801
The Assignment of the different Poll Intervals for each point is done inside the Panelbus Point Discovery Dialog.
Panel-Bus cable type and length
See CIPer Model 50 Installation and Commissioning Instructions 31- 00233EFS for all details.
Max. Panel Bus length:
120 ft for any type of cabling and topology. No additional end termination is permitted.
2400 ft for twisted-pair or telephone cable and daisy chain topology. The Controller must be
positioned at one end of the Panel-Bus, and an end termination (120 Ω) at the other end.
Furthermore, the three-position slide switch must be set to "END." Use Honeywell cable 3322 or
3251.