WEBs CIPer Model 50 – USER GUIDE 
 
 25    31-00198—01   
 
The Assignment of the different Poll Intervals for each point is done inside the Panelbus Point Discovery Dialog. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Panel-Bus cable type and length 
 
See CIPer Model 50 Installation and Commissioning Instructions 31- 00233EFS for all details. 
 
 
Max. Panel Bus length: 
 
120 ft for any type of cabling and topology.  No additional end termination is permitted. 
 
2400  ft  for  twisted-pair  or  telephone  cable  and  daisy  chain  topology.  The  Controller  must  be 
positioned  at  one  end  of  the  Panel-Bus,  and  an  end  termination  (120  Ω)  at  the  other  end. 
Furthermore, the three-position slide switch must be set to "END." Use Honeywell cable 3322 or 
3251.