3.2.10.3 Modbus Data Input
1. On the CIU 888 node, right-click and choose Import MODBUS
device type file.
NOTE: Modbus device configuration file for Honeywell Smartline level transmitter
SLG700 is available by default in the CIU 888 Service tool. For new field
device, import its Modbus device configuration file to the CIU 888 Service tool.
2. Device Type- CIU 888 Service Tool window appears.
3. Select the XML of the Modbus device and click Open.
The details of the specified XML file are loaded.
Refer to Appendix H for the creation of a new Modbus field device
configuration file.