Getting Started
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 53
$*6
GSV calculation type This setting provides a list of GSV calcula-
tion methods (Liquid calculation methods)
supported.
Selection:
Default: No Liquid calculation method
Note: The following methods are only
available when Calculation type is
selected as CIU 888 calculations.
a) ASTM D4311-15 API @ 60 F
b) ASTM D4311M-15 kg/m3 @ 15 C
c) ASTM D1555-2016 API @ 60 F
d) ASTM D1555M-2016 kg/m3 @ 15 C
e) EN15940- 2019
f) SGS-2021
g) NBR15639-2016
h) User Configurable Density table
i) User Configurable CTL table
j) User Configu rable Concentration table
Alpha Type This setting indicates how Alpha (Product
TC) should be interpreted.
Selection: Alpha60
Default: Alpha60
Product code/commodity This setting indicates which product type
to be applied for the selected GSV Calcu-
lation type.
Reference temperature Product Reference Temperature.
The volume of the product in a tank varies
with changes of ProdTemp.
This causes changes in the product level
which result in incorrect volume calcula-
tions.
ProdTRef is used to get calculation results
(volumes, mass) which are independent of
the temperature of the product in the tank
at the time of the measurement.
Alpha Product Temperature Coefficient.
Manual:
Only with Product Code C the ProdTC is
entered manually.
It must be entered in 10e-7 format (shift
the decimal separator 7 positions to the
right), e.g. 0.000612 is entered as 6120
With Product Codes A, B and D, ProdTC
is calculated and not used with other cal-
culations.
With Product Code E it is not used at all.
Properties Description