Honeywell | 70
10 Troubleshooting
10 Troubleshooting
Log Representation
LEDError A
Diagnostic Log B
Event Log C
Cellular Log D
Alarm Log E
ML Error Code F
MasterLink
Error Codes
Issue/Error Log
Troubleshooting Recom-
mendations
223
Self Test Failure - Radio SoC mal-
function or insufficient power supply
B
Flash memory Read/Write failure.
1. Check Power supply.
2. Allow supercap to charge
at least 1 hour and then try
rebooting the device.
224 Self Test Failure - Flash 1 B
1. Power Cycle the unit.
2. If the problem persists
even after reboot, then
replace the device.
225 Self Test Failure - Flash 2 B
Flash memory Read/Write failure.
1. Power Cycle the unit.
2. If the problem persists
even after reboot, then
replace the device.
11, 226 Self Test Failure - SRAM A, B
SRAM memory Read/Write fail-
ure.
1. Power Cycle the unit.
2. If the problem persists
even after reboot, then
replace the device.