10 Technical Data
enCore FC
Operating Instructions
Page 113 of 120
10.5.1 Data protocols and its TCP default port (Ethernet)
Protocol Default
port
Description
HTTP
80
HyperText Transfer Protocol allows e.g. to
access the enCore device via the remote
operation panel.
MMS
102
Manufacturing Messaging Specification
(acc. to ISO standard 9506) allows
communication between enSuite and
enCore devices.
Modbus TCP
502
Protocol for the data exchange of user-
defined registers between a central control
station and enCore devices over a standard
TCP/IP network.
NTP
123
Network Time Protocol for the highly
accurate time synchronization of enCore
devices with an NTP time server.
DSfG
8000
Digitale Schnittstelle für Gasmessgeräte
(digital interface for gas measuring devices)
allows communication in a heterogeneous
network of different DSfG-compatible
devices. DSfG is a digital data protocol that
is well-established in Germany.
Tabelle 10-1: Default ports used by enCore devices

Table of Contents

Other manuals for Honeywell enCore FC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell enCore FC Series and is the answer not in the manual?

Honeywell enCore FC Series Specifications

General IconGeneral
BrandHoneywell
ModelenCore FC Series
CategoryDesktop
LanguageEnglish

Related product manuals