MS-5UD & MS-10UD Series Manual — P/N 52626:C2  1/24/2012 13
Section 1: Product Description
The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone 
FACP.  The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise 
specified.  The combination control and digital communicator panels provide reliable fire signaling 
protection for small to medium sized commercial, industrial and institutional buildings.  The FACP 
is compatible with System Sensor’s i
3
 detectors which are conventional smoke detectors that can 
transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervi-
sory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 
45
o
 F (refer to System Sensor i
3
 Installation and Maintenance Instructions).  In addition, the control 
panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire 
smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact 
devices.  Refer to the Fire•Lite Device Compatibility Document for a complete listing of compati-
ble devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays 
(factory programmed for Alarm,  Trouble and Supervisory) and 24 VDC special application reset-
table and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery level 
and telephone line integrity.  Available accessories include local and remote upload/download soft-
ware, remote annunciators and reverse polarity/city box transmitter. 
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via 
the public switched telephone network.  It also allows remote programming or interrogation of the 
control panel using the PS-Tools Upload/Download utility via the public switched telephone net-
work.  Local programming interrogation is also possible using the PS-Tools and the USB port on 
the FACP.  Any personal computer with Windows
®
 XP or newer, compatible modem with a speed 
of 2400 baud and PS-Tools may serve as a Service Terminal.  This allows download of the entire 
program or upload of the entire program, history file, walktest data and current status.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will 
activate audible and visual signaling devices, illuminate an indicating LED, display alarm informa-
tion on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and 
operate an optional module used to notify a remote station or initiate an auxiliary control function.