152 MS-5UD & MS-10UD Series Manual — P/N 52626:C2  1/24/2012
Appendix C: FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron Receiver/Transmit-
ter. 
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20 
feet and enclosed within conduit or equivalently protected against mechanical injury. 
P
CAUTION: POSSIBLE EQUIPMENT DAMAGE
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON 
MODULES ARE NOT SHOWN IN ACTUAL ORDER.  FOLLOW KELTRON MANUAL AND 
MODULE MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE 
DAMAGE!
   Fire Alarm Control Panel
(terminal blocks are not shown in their 
actual positions in order to clarify wiring 
connections)
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Note:  Cut TBL jumper on 4XTMF module to send 
alarm/trouble signal from the same pair or terminals.
Alarm/Trouble SignalSprinkler Supervisory Signal
*Note: For more 
information, refer to the  
Keltron manual.
4XTMF Module
Figure C.1  Keltron Wiring