MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012 87
Master Programming Level Programming
ANN-RLY Options Screen
Pressing 3 for ANN-RLY Options while viewing ANN-BUS Screen #2 will cause the following
screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various func-
tions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display the
remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen,
press the number key corresponding to the relay to be programmed. Following is a list of the avail-
able programming options for each relay:
General Alarm
General Trouble
General Supervisory
•AC Loss
Waterflow Delay
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
Input Zone 7
Input Zone 8
Input Zone 9
Input Zone 10
Silenceable Alarm
Not Assigned
ANN-AUDIO Options Screen
Pressing 1 for ANN-AUDIO Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen
PROGRAMMING
1=ANN-AUDIO OPTIONS
ANN-BUS Screen #3
ANN-AUDIO OPTIONS
1=ALL CALL ZONE 1
ANN-AUDIO Options