Appendix D: Wire Requirements
Connecting external system accessories to the main circuits must be carefully considered to ensure 
proper operation.  It is important to use the correct type of wire, gauge and run length for each cir-
cuit.  Reference the chart below to specify wire requirements and limitations for each circuit.  
CIRCUIT CONNECTIONS WIRE REQUIREMENTS
Circuit Type Circuit Function
Wire Type and 
Limitations
Recommended 
Max. Distance
Feet (meters)
Wire Gauge
Initiating Device 
Circuit
(power-limited)
Connects to 
Initiating Devices
Untwisted, unshielded wire 
(maximum loop resistance 
not to exceed 100 ohms)
Distance limitation 
set by 100 ohm 
resistance limitation
12-18 AWG (3.25 - 0.75 mm
2
)
ANN-BUS  (EIA-
485)
power-limited
Communication for 
ANN-BUS 
annunciator and 
relay modules
Twisted pair a maximum 
loop resistance of 120 
ohms
6,000 (1,800 m) 12-18 AWG (3.25 - 0.75 mm
2
)
ANN-BUS 
Power
Power for 
ANN-BUS 
annunciators
Refer to Table 2.1, “Wiring Distances,” on page 42 for information on device wiring
24 VDC 
Regulated, 
resettable, 
nonresettable
Power for 
accessories and 
4-wire devices
Untwisted, unshielded wire Distance limitation 
set by 4 volt 
maximum line drop
12-18 AWG (3.25 - 0.75 mm
2
)
Auxiliary Trouble 
Input
Open Collector 
trouble input for 
CHG-75, 
CHG-120F, etc.
Single conductor Distance limitation 
20 feet in same 
room
18 AWG (0.75 mm
2
)
Remote Sync 
Output
Provides strobe 
and normal sync 
for remote NAC 
power supplies
Untwisted, unshielded pair 
wire
Distance set by 295 
ohm resistance 
limitation
12-18 AWG (3.25 - 0.75 mm
2
)
NAC Outputs Connects to NAC 
devices or Release 
devices
Untwisted, unshielded pair 
wire
Refer to Section D.1 and Section D.2 on page 154.
Table D.1  FACP Wire Specifications