MS-5UD & MS-10UD Series Manual — P/N 52626:C2  1/24/2012 29
Operating Power Installation
may be connected to this circuit.  In addition, this circuit must be provided with overcurrent protec-
tion and may not contain any power disconnect devices.  An Earth Ground connection must be 
made to ensure proper panel operation and lightning and transient protection.  Connect the Earth 
Ground wire [minimum 14 AWG (2.00 mm
2
)] to the grounding stud in the backbox and then run 
the wire to TB1.  Do not use conduit for the Earth Ground connection since this does not provide 
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery.  Connect the battery cable to J12 on the main circuit 
board using the plug-in connector and cable provided.  The battery charger is current-limited and 
capable of charging sealed lead acid batteries.  The charger shuts off when the system is in alarm.
WARNING: SULFURIC ACID
BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN 
AND EYES AND CAN DESTROY FABRICS.  IF CONTACT IS MADE WITH SULFURIC ACID, 
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK 
IMMEDIATE MEDICAL ATTENTION. 