Programming
MS-9050UD PN 52413:C 01/23/08 127
3+1, 4+1 Express and 4+1 Standard
The information shown in Table 3.3 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 0 for an Event Code
Setting to disable the report.
Table 3.3 Event Codes
Event Description Event Code Settings
Active Restoral
PULL STATION 1 E
MON-USER-DEF-1 1 E
WATERFLOW 1 E
MON-USER-DEF-2 1 E
SMOKE (PHOTO) 1 E
DET-USER-DEF-1 1 E
SMOKE (ION) 1 E
DET-USER-DEF-2 1 E
HEAT DETECT 1 E
DET-USER-DEF-3 1 E
SMOKE DUCT-P 1 E
DET-USER-DEF-4 1 E
PHOTO W/HEAT 1 E
DET-USER-DEF-5 1 E
DUCT SUPERVISORY 8 E
DET-USER-DEF-6 8 E
PHOTO SUPERV 8 E
DET-USER-DEF-7 8 E
not used 0 0
not used 0 0
not used 0 0
not used 0 0
MONITOR 1 E
MON-USER-DEF-3 1 E
not used 0 0
not used 0 0
SMOKE CONVEN 1 E
MON-USER-DEF-5 1 E
HEAT CONVEN 1 E
MON-USER-DEF-6 1 E
MEDIC ALERT 0 0
MON-USER-DEF-7 0 0
HAZARD ALERT 0 0
MON-USER-DEF-8 0 0
TORNADO ALRT 0 0
MON-USER-DEF-9 0 0
not used 0 0
not used 0 0
TAMPER 8 E
MON-USER-DEF-11 8 E
MON SUPERVISORY 8 E
MON-USER-DEF-12 8 E
MON SUPERV AUTO 8 E
MON-USER-DEF-13 8 E
HVAC OVRRIDE 8 E
POWER MON 6 A