Programming
128 MS-9050UD PN 52413:C 01/23/08
1. The FACP will not transmit a TOTAL COMM FAULT message to the Central Station upon
communication restoral. This event code is used only for a local indication of a communication
fault.
MON-USER-DEF-14 6 A
TROUBLE MON POINT_FAULT code will always be transmitted
MON-USER-DEF-15 POINT_FAULT code will always be transmitted
PROCESS MON 0 0
MON-USER-DEF-16 0 0
PROCMON AR 0 0
MON-USER-DEF-17 0 0
not used 0 0
not used 0 0
POINT_FAULT F D
POINT_DISABLE 4 5
AC_FAIL 9 3
DRILL B C
SLC 1 OPEN FAULT 6 A
SLC 1 SHORT FAULT 6 A
GROUND FAULT 6 A
LOW BATTERY 6 A
NO_BATTERY 6 A
TELCO LINE 1 6 A
TELCO LINE 2 6 A
COMM FAULT 1 6 A
COMM FAULT 2 6 A
TOTAL COMM FLT
1
00
PRINTER FAULT 6 A
NAC 1 FAULT 6 A
NAC 2 FAULT 6 A
27V SYS PWR FAULT 6 A
not used 0 0
NAC 1 DISABLE 4 5
NAC 2 DISABLE 4 5
CS CALC FAULT 6 A
CHARGER FAULT 6 A
OPTION CARD 1 FAULT 6 A
ANN-BUS PWR FAULT 6 A
ZONE DISABLE 4 5
MODEM CHIP FAULT 6 A
ANN-BUS COMM FAULT 6 A
NO_DEVICES_INSTLLD 6 A
OFF_NORMAL_MESSAGE 6 A
24_HOUR_TEST 9 0
24 HOUR ABNORMAL TES F 0
UPDOWN REQUEST 7 0
UPLOAD SUCCESS 7 0
DOWNLOAD SUCCESS 7 0
UPDOWN FAILURE 7 0
GENERAL_ALARM 0 0
GENERAL_SUPERVISORY 0 0
Table 3.3 Event Codes (continued)