Programming
MS-9050UD PN 52413:C 01/23/08 129
4+2 Standard, 4+2 Express, 3 + 1, 4 + 1 and 4+2 Expanded Formats
The information shown in Table 3.4 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 00 for an Event Code
Setting to disable the report.
Table 3.4 Event Codes
Event Description Event Code Settings
Active Restoral
PULL STATION 11 E1
MON-USER-DEF-1 11 E1
WATERFLOW 11 E1
MON-USER-DEF-2 11 E1
SMOKE (PHOTO) 11 E1
DET-USER-DEF-1 11 E1
SMOKE (ION) 11 E1
DET-USER-DEF-2 11 E1
HEAT DETECT 11 E1
DET-USER-DEF-3 11 E1
SMOKE DUCT-P 11 E1
DET-USER-DEF-4 11 E1
PHOTO W/HEAT 11 E1
DET-USER-DEF-5 11 E1
DUCT SUPERVISORY 81 E1
DET-USER-DEF-6 81 E1
PHOTO SUPERV 81 E1
DET-USER-DEF-7 81 E1
not used 00 00
not used 00 00
not used 00 00
not used 00 00
MONITOR 11 E1
MON-USER-DEF-3 11 E1
not used 00 00
not used 00 00
SMOKE CONVEN 11 E1
MON-USER-DEF-5 11 E1
HEAT CONVEN 11 E1
MON-USER-DEF-6 11 E1
MEDIC ALERT 00 00
MON-USER-DEF-7 00 00
HAZARD ALERT 00 00
MON-USER-DEF-8 00 00
TORNADO ALRT 00 00
MON-USER-DEF-9 00 00
not used 00 00
not used 00 00
TAMPER 81 E1
MON-USER-DEF-11 81 E1
MON SUPERVISORY 81 E1
MON-USER-DEF-12 81 E1
MON SUPERV AUTO 81 E1
MON-USER-DEF-13 81 E1
HVAC OVRRIDE 81 E1