Programming
130 MS-9050UD PN 52413:C 01/23/08
1. The FACP will not transmit a TOTAL COMM FAULT message to the Central Station upon
communication restoral. This event code is used only for a local indication of a communication
fault.
POWER MON 81 E1
MON-USER-DEF-14 81 E1
TROUBLE MON POINT_FAULT code will always be transmitted
MON-USER-DEF-15 POINT_FAULT code will always be transmitted
PROCESS MON 00 00
MON-USER-DEF-16 00 00
PROCMON AR 00 00
MON-USER-DEF-17 00 00
not used 00 00
not used 00 00
POINT_FAULT F1 D1
POINT_DISABLE 41 51
AC_FAIL 92 93
DRILL 97 98
SLC 1 OPEN FAULT 43 53
SLC 1 SHORT FAULT 44 54
GROUND FAULT 61 A1
LOW BATTERY 62 A2
NO_BATTERY 63 A3
TELCO LINE 1 64 A4
TELCO LINE 2 65 A5
COMM FAULT 1 6A AA
COMM FAULT 2 6B AB
TOTAL COMM FLT
1
00 00
PRINTER FAULT 6C AC
NAC 1 FAULT 66 A6
NAC 2 FAULT 67 A7
27V SYS PWR FAULT 45 55
not used 00 00
NAC 1 DISABLE 4B 5B
NAC 2 DISABLE 4C 5C
CS CALC FAULT 46 56
CHARGER FAULT 47 57
OPTION CARD 1 FAULT 48 58
ANN-BUS PWR FAULT 49 59
ZONE DISABLE 42 52
MODEM CHIP FAULT 49 59
ANN-BUS COMM FAULT 49 59
NO_DEVICES_INSTLLD 4A 5A
OFF_NORMAL_MESSAGE 6F AF
24_HOUR_TEST 99 00
24 HOUR ABNORMAL TES FB 00
UPDOWN REQUEST 71 00
UPLOAD SUCCESS 72 00
DOWNLOAD SUCCESS 73 00
UPDOWN FAILURE 74 00
GENERAL_ALARM 00 00
GENERAL_SUPERVISORY 00 00
Table 3.4 Event Codes (continued)