Programming
MS-9050UD PN 52413:C 01/23/08 79
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type
Screens:
While viewing one of the Control Type screens, select the type of control module being
programmed by pressing the corresponding keypad number key. The display will return to the
Edit Control Screen #2 and indicate the new type selection.
Notes:
1. A control relay module set to the Resettable Power type will follow the main circuit board 24
VDC resettable power unless the control relay module is disabled.
The following table contains control module type codes and their functions which are displayed
in the Control Type screens:
Note: For HVAC SHUTDN description, refer to "Control Module Operation" on page 198.
Control Type Special Function
Blank NAC Type - Supervised
Bell Circuit NAC Type - Supervised
Horn Circuit NAC Type - Supervised
Sounders NAC Type - Supervised
Relay Ignore Open Circuit
Strobe Circuit NAC Type - Supervised
Control NAC Type - Supervised
Resettable Power Relay Type - Ignore Open Circuit
HVAC SHUTDN Relay Type - Ignore Open Circuit
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1