10260A Series Actuators Installation, Operations, and Maintenance Manual
10 10260A Series Actuators – Installation, Operations, and Maintenance 2/03
Specification - Actuator with Output Board
Electrical
Feedback signals 0-20 mA
4-20 mA
1-5 Vdc with 250 ohm resistor ± 0.1 %
0-16 Vdc with 800 ohm resistor ± 0.1 %
Slidewire Emulation Provides output voltage ratiometric to shaft position and potentiometric to supply
voltage (1-20 Vdc) without a slidewire. Emulates a 100 ohms to 1000 ohm slidewire.
10 mA output maximum.
Isolation Output is isolated from power and input signal by 240 Vac
Load Requirement (4-20) Current Out — 0-1000 ohms