IFS-2600 Installation & Programming Manual Page 27
P/N 10069 ECN08-0066
PROGRAMMING
GLOBAL OPTIONS
ANCILLARY TRIP
1 LATCHING NORMALLY DE-ENERGISED
2 NON-LATCHING NORMALLY DE-ENERGISED
3 LATCHING NORMALLY ENERGISED
4 NON-LATCHING NORMALLY ENERGISED
ALARM VERIFICATION
1 DISABLED
2 2 MINUTES
3 3 MINUTES
4 4 MINUTES
5 5 MINUTES
TIME
(DD) / (MM) / (YY)
(HH) : (MM)
ZONE OPTIONS
DESCRIPTION INPUT DELAY
1 Standard Latching 2 seconds
2 Standard Latching 2 seconds with AVF
3 Non Latching 2 seconds
4 Non Latching 20 seconds
5 Time Delay 10 seconds
6 Time Delay 20 seconds
7 Time Delay 30 seconds
8 Time Delay 40 seconds
9 Time Delay 50 seconds
10 Time Delay 60 seconds
Type Output Description
1 Indicate Only
2 Indicate, Bell
3 Indicate, Bell, General Alarm
4 Indicate, Bell, General Alarm, Ancillary
5 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1
6 Indicate, Bell, General Alarm, Ancillary Brigade Relay #2
7 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER IFS-2600 and is the answer not in the manual?

Honeywell NOTIFIER IFS-2600 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER IFS-2600
CategoryFire Alarms
LanguageEnglish

Related product manuals