Page 42 IFS-2600 Installation & Programming Manual
P/N 10069 ECN08-0066
FAULT/ISOLATE MAPPING
FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the
fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if
any one of up to five (5) zones go into fault/put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault/(or
are manually put in isolate) will cause the relay to operate.
ISOLATE MAPPING
ISOLATE MAPPING works the same as or mapping of alarm except it relates to the isolate flag on
each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to
five zones is put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3, if put in isolate will
cause the relay to operate.