NCD Instruction Manual — P/N LS10210-051NF-E:C 2/18/2019 35
Other: Events that are listed as Other are as follows: Operation
4.6 Other: Events that are listed as Other are as follows:
Events listed as Other are as
follows:
• CO Pre-Alarm (blue).
• Critical Processes
(yellow).
• Security (blue).
• Pre-Alarm (red).
• Hazard/Weather Alert
(Yellow).
When more than one of
these conditions have been
activated they will be listed
in order of priority. CO-Pre
Alarm will be listed first,
followed by Critical Pro-
cesses, Security, Pre-Alarm
and Hazard/Weather Alert.
4.6.1 Responding to an Other event.
To acknowledge an Other event and silence the NCD sounder do the following:
• The Informational Text Area on the screen will indicate step by step what needs to be done to acknowledge and silence the event.
• Tap on the
ACKNOWLEDGE touch point located in the Header Bar. The acknowledge touch point will be highlighted in blue. A check
mark will appear next to the acknowledged event.
• BLOCK ACKNOWLEDGE allows for multiple events to be acknowledged at once.
• Tap on the SILENCE touch point located in the Header Bar. The SILENCE icon in the Alert Bar will illuminate blue once the NCD is
silenced.
• Once all the events have been acknowledged the blue highlight indicator will move from the
ACKNOWLEDGE touch point to the
SILENCE touch point.
•Tap RESET for an latched event.
Figure 4.6 Other Event Screen
1:38:06PM
CO ALARM
SUPERVISORY
TROUBLE
DISABLE
SIGNALS
SILENCED
FIRE ALARM
SECURITY ALARM
SECURITY ALARM
SECURITY L
Zone Z553 (Z553)
Thu 02/22/18
1:52:57 PM
NO25L01M011
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
UNACKNOWLEDGED SECURITY ALARMS(1)
OTHER
1