In case there are Alarms from more than one gas detector the alarm screen will present
the information of the different channels, as follows:
• The information is sorted according to its importance: Off-Scale, Alarm3, Alarm2,
Alarm1;
• Off-Scale is considered an Alert state with the highest importance.
By selecting an Alarm event and pressing the Enter key, a further screen will appear
showing the details of the event.
Fig. 3-5) Alarm 1 event details
From the main screen, by pressing the MENU button and selecting ACTIVE EVENTS it
will be possible to view the channels in Alarm/Fault and not yet reset.
FAULT
The Fault status will be activated under the following conditions:
1. Short circuit, open circuit or channel failure
2. Detector in Low Chamber Value (signal below "0") 3. Out-of-scale detector
(signal above 100% of scale)
Fig. 3-6) Fault status screen
Selecting a Fault event and pressing the Enter key, a further screen will appear showing
details of the event.