NFG-8
NFG-8_manu-inst_ITA
Installation and Operation
Manual Doc. M-040.1-NFG8-EN
Rev A.3
PAGE - 11
NOTIFIER ITALY
3.3)
MENU
In normal status, in the main screen appears the list of gas detectors managed by the
central unit. Pressing the MENU button, the sub-menus described below will appear
with the relative function.
INSERT
changes the status of the sensors and/or relays from Off to
On.
DISINSERT
changes the status of the sensors and/or relays from
switched on to switched off.
TEST
selects the Test mode for sensors and relays
END OF TEST
restores normal operation of the sensors or relays in Test
ALARM THRESHOLDS
allows you to view and/or modify the alarm thresholds of the
sensors
RELEASE DELAY
allows you to view and/or modify the delay times
activation and deactivation of the relays
LOG EVENTS
allows you to consult the event history
SYSTEM INFO
information about the control unit (name, FW and HW
versions)
etc.)
ACTIVE EVENTS
(appears only if there are active events i.e. Alarms or Faults
not
reset)
3.4)
ACTIVE EVENTS and event management
If you select ACTIVE EVENTS and press ENT, a list will show the current active events.
If Alarms and Faults/Emergency are present at the same time, these will be shown on
two screens.
Alarms screen
Faults Screen
Fig. 3-8) Active Events screens
In case of a new event, the screen will automatically switch to the ACTIVE EVENTS
screen and the unit's internal buzzer will sound. Until ACK is performed for the new
event, it will not be possible to return to the main screen.
The screens in Figure 3.5.1 show events for which ACK has not yet been performed.
Once the event has been acknowledged (ACK performed), an "X" is shown in the right
column.
In case of Active Events, it is possible to perform 3 operations:
-Press ENT for more details on the event
Press ACK to acknowledge the event and silence the central unit buzzer.