EasyManua.ls Logo

Honeywell NOTIFIER RP-2002C - FACP Operation

Honeywell NOTIFIER RP-2002C
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RP-2002 Series Manual — P/N 53039:E6 1/26/2017 123
Template 8: Single Hazard, Single Detector - Bell/Horn/Strobe FACP Configuration Templates
AC Loss Delay Timer - set for 2 hours
FACP Operation
Input Zone 1 (2-Wire Smoke) Activation:
Output 1 (Release Circuit 1 will perform an agent release following a 30 second Pre-Discharge
delay and remains on until panel reset.
Output 2 (Alarm NAC) will turn on steady until discharge, it will then turn off.
Output 3 (Release Stage Coded) will pulse at 1/2 second on, 1/2 second off until discharge, it
will then turn on steady.
Output 4 (Release Stage Discharge) will turn on steady upon discharge.
Input Zone 2 (2-Wire Smoke) Activation:
Output 1 (Release Circuit 1 will perform an agent release following a 30 second Pre-Discharge
delay and remains on until panel reset.
Output 2 (Alarm NAC) will turn on steady until discharge, it will then turn off.
Output 3 (Release Stage Coded) will pulse at 1/2 second on, 1/2 second off until discharge, it
will then turn on steady.
Output 4 (Release Stage Discharge) will turn on steady upon discharge.
Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) begins agent release and remains on until reset.
Output 3 (Release Stage Coded) will turn on steady.
Output 4 (Release Stage Discharge) will turn on steady.
Input Zone 4 (Abort Release Switch) Activation only:
Pre-Discharge Timer will continue to count down until it reaches 10 seconds and then stop.
Releasing the Abort Release Switch will allow the Pre-Discharge Timer to continue its count
down from 10 second. If the Abort Release Switch is again activated before the Pre-Discharge
Timer reaches 0, the Timer will reset to 10 seconds and hold.
Input Zone 5 (Discharge Pressure Switch) Activation:
Output 3 (Release Stage Coded) will turn on steady.
Output 4 (Release Stage Discharge) will turn on steady
Input Zone 6 (Supervisory) Activation:
No output circuits will be activated. FACP will indicate a supervisory condition
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire
Smoke) or Zone 3 (Manual Release) or Zone 5 (Discharge Pressure Switch) will operate Alarm
Relay
Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay
Supervisory (Tracking) - activation Input Zone 6 (Supervisory), the disabling of Releasing
Circuit or any other system supervisory will operate the Supervisory Relay

Table of Contents

Related product manuals