EasyManua.ls Logo

Honeywell NOTIFIER RP-2002C - FACP Operation

Honeywell NOTIFIER RP-2002C
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
132 RP-2002 Series Manual — P/N 53039:E6 1/26/2017
FACP Configuration Templates Template 11: Agent/Waterflow - Cross-Zone
ANN-BUS
Enabled = Yes
Address 1: ANN-RLY
Timers
Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 0 seconds
Discharge: Release 1 - set for Always On; Release 2 - set for Always On
Waterflow Delay Timer - set for 90 seconds
AC Loss Delay Timer - set for 2 hours
FACP Operation
Input Zone 1 (2-Wire Smoke) Activation only:
Output 3 (Alarm NAC) will turn on steady.
Input Zone 2 (2-Wire Smoke) Activation only:
Output 3 (Alarm NAC) will turn on steady.
Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) agent release remains on until reset.
Output 2 (Release Circuit 2) agent release remains on until reset.
Output 4 (Release Stage Coded) will turn on steady.
Input Zone 3 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 1 will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
Input Zone 4 (Discharge Pressure Switch) Activation only:
Output 3 (Alarm NAC) will turn on steady.
Output 4 (Release Stage Coded) will turn on steady
Input Zone 5 (Waterflow) Activation only (following 90 second Waterflow Delay):
Output 3 (Alarm NAC) will turn on steady.
Input Zone 6 (Supervisory) Activation only:
No output circuits will be activated. FACP will indicate a supervisory condition
Input Zone 1 (2-Wire Smoke) and Input Zone 2 (2-Wire Smoke) Activation together:
In addition to the individual events that will occur for each Input Zone as detailed above, the
Pre-Discharge Timer will begin to count down. Output (Release Circuit 2) will activate. Output
3 will turn off. Output 4 will pulse 1/2 second on, 1/2 second off while the Pre-Discharge
Timer for Release Circuit 1 is counting down. When the Pre-Discharge Timer reaches 0,
Output 1 (Release Circuit 1) will begin the agent release which will continue until reset.
Output 4 will turn on steady when discharge for Release Circuit 1 begins.
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire
Smoke) or Zone 3 (Manual Release) or Zone 4 (Discharge Pressure Switch) or Zone 5
(Waterflow) will operate Alarm Relay
Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay
Supervisory (Tracking) - activation Input Zone 6 (Supervisory), the disabling of Releasing
Circuit or any other system supervisory will operate the Supervisory Relay

Table of Contents

Related product manuals