1. Align the two mounting holes in the transmitter with the two slots in the mounting bracket and
assemble the (2) M8 hex cap screws, (2) lockwashers and (2) flat washers provided. Rotate
transmitter assembly to the desired position and torque the M8 hex cap screws to 27,0 Nm/20,0
Lb-ft maximum.
2. Pipe Mount Option: Refer to
Figure 3-5. Position the bracket on a 2-inch (50.8 mm) horizontal
or vertical pipe, and install a U” bolt around the pipe and through the holes in the bracket.
Secure the bracket with the nuts, flat washers and lock washers provided.