Honeywell SmartLine STIW400 - Appendix A - Modbus

Honeywell SmartLine STIW400
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68 SmartLine Wireless Temperature and Universal I/O User's Manual Revision
3
Appendix A - Modbus
Name Description Data Type Data Size Access Class Enum Value Enum Description
UAP_STREV Field device application static data revision level. Uint16 2 Read Only Static Revision
CTS_VERSION Field device application CTS version. Uint16 2 Read Only Static
ITS_VERSION Field device application ITS version. Uint16 2 Read Only Static
DIAG_STATUS Field device application diagnostic status bitstring. BitString 4 Read Only Dynamic
2147483648 - Failure Status Failure status
1073741824 - Function Check Status Function check status
536870912 - Out of Speci fication Status Out of specification status
268435456 - Mainte nance Re quired Status Maintenance required status
134217728 - Fault i n Electronics Faults in electronics
67108864 - Fault i n Sensor Faults in sensor
33554432 - Installati on or Calibration Problem Installation or calibration problem
16777216 - Out Of Service At least one Transducer is OOS
131072 - Manual Mode Active At least one Transducer is in Manual Mode
1048576 - Power is Criti call y Low Power is critical low: maintenance needed
128 - Calibration Error Error in Calibration
1 - Detail Information Available Detail information available
UAP_OPTION Option BitString 2 Read/Write Static
8192 - Enable Software Write Protect Enable Software Write Protect
UAPMO_ALERT No Help Available Uint8 1 Read/Write Static
0 - Begin Alert Recovery No Help Available
1 - End Alert Recovery No Help Available
2 - Device Restart No Help Available
3 - Maintenance Alert No Help Available
4 - Out of Specification Alert No Help Available
5 - Function Check Alert No Help Available
6 - Failure Status Alert No Help Available
DIAG_STATUS_DETAIL_1 Device self-diagnosis information BitString 4 Read Only Dynamic
1 - Electronics Failure An electronic component has failed
4 - Input Failure Input failure
16 - Low Battery Battery needs replacement
128 - Calibration Error Persistent calibration error
SENSOR_DEVREV Device Revision Uint16 2 Read Only Static
SENSOR_BUILD Software Version Uint16 2 Read Only Static
MAINTENANCE_ALERT Maintenance Alert BinaryAlarmDesc 2 Read/Write Static
MAINTENANCE_ALERT.ALERT_DISABLE Enable or Disable the Alert Boolean 1 Read/Write Static
MAINTENANCE_ALERT.ALERT_PRIORITY Priority set for the Alert Uint8 1 Read/Write Static
OUT_OF_SPEC_ALERT Out of Specification Alert BinaryAlarmDesc 2 Read/Write Static
OUT_OF_SPEC_ALERT.ALERT_DISABLE Enable or Disable the Alert Boolean 1 Read/Write Static
OUT_OF_SPEC_ALERT.ALERT_PRIORITY Priority set for the Alert Uint8 1 Read/Write Static
FUNCTION_CHECK_ALERT Function Check Alert BinaryAlarmDesc 2 Read/Write Static
FUNCTION_CHECK_ALERT.ALERT_DISABLE Enable or Disable the Alert Boolean 1 Read/Write Static
FUNCTION_CHECK_ALERT.ALERT_PRIORITY Priority set for the Alert Uint8 1 Read/Write Static
FAILURE_STATUS_ALERT Failure Status Alert BinaryAlarmDesc 2 Read/Write Static
FAILURE_STATUS_ALERT.ALERT_DISABLE Enable or Disable the Alert Boolean 1 Read/Write Static
FAILURE_STATUS_ALERT.ALERT_PRIORITY Priority set for the Alert Uint8 1 Read/Write Static
POWER_SOURCE Power source Uint8 1 Read Only Dynamic
1 - Battery Module Powered by internal battery
2 - 24V External Power Modul e Powered using 24V external power