Revision 1 SmartLine Wireless Temperature and Universal I/O User's Manual 69
Name Description Data Type Data Size Access Class Enum Value Enum Description
V_POWER Power voltage Float 4 Read Only Dynamic
DL_ALIAS_16_BIT Field device radio short address. Uint16 2 Read Only Static
DEVICE_ROLE_CAPABILITY Field device radio role capability. Ui nt16 2 Read Only Constant
128 - Provisioning Device Provisioning Device
64 - System Time Source System Time Source
32 - Security Manager Security Manager
16 - System Manager System Manager
8 - Gateway Gateway
4 - Access Point Access Point
2 - Routing Device Routing Device
1 - I/O Device I/O Device
POWER_SUPPLY_STATUS Field device power supply status. Uint8 1 Read Only Dynamic
0 - Line Powered Line Powered
1 - Battery High
2 - Battery Medium
3 - Battery Low
JOIN_COMMAND Field device radio join command. Uint8 1 Read/Write Static
0 - None None
2 - Warm Restart Warm Restart
3 - Restart as Provisioned Restart as Provisioned
RESTART_COUNT Field device radio restart counter. Uint16 2 Read Only Static
UPTIME Field device radio uptime. Uint32 4 Read Only Dynamic
DROP_OFF_COUNT Field device radio network drop off counter. Uint16 2 Read Only Static
JOIN_ATTEMPT_COUNT Field device radio network join attempt counter. Uint16 2 Read Only Static
RESET_COUNTERS Field device radio reset counters command. Boolean 1 Read/Write Static
ROUTING_ASSIGNMENT Field device radio network routing assignment. Uint8 1 Read/Write Static
0 - Routing Disabled Routing Disabled
1 - Routing Enabled Routing Enabled
2 - Not Applicable Not Applicable
Table A-1: Device Level Modbus Table