7. Operation
7.2. Transmitter PV display
Revision 1 SmartLine Wireless Temperature and Universal I/O User's Manual 49
Table 7-5: SmartLine TEMP-UIO units
Temperature Description
degC Celsius
degF Fahrenheit
RTD, 2W and 3W resistance
Ohm Ohm
% Percent
Voltage
mV Millivolts
HLAI
mA Milliamps
% Percent
Digital Input and Digital Output
ON/OFF ON or OFF state
Table 7-6: Radio menu
RADIO Radio menu
PRI RSSI Primary receive signal strength. Read only. Signal strength 00 is too weak
to connect to the network.
Displayed Value Value dBm Rx Margin dB
00 < -86 < 10
01 -86 to -81 10 to 15
02 -80 to -75 16 to 21
03 -74 to -69 22 to 27
04 -68 to -63 28 to 33
05 -62 to -57 34 to 39
06 -56 to -51 40 to 45
07 -50 to -45 46 to 51
08 -44 to -11 52 to 85
09 ≥ -10 Saturation