EasyManua.ls Logo

Honeywell SMX-AUS - ENABLE OR DISABLE - LOGIC ZONE

Honeywell SMX-AUS
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User’s Guide SMX-AUS
28 NS-MN-0032 / 11.2020
7.2.3 ENABLE OR DISABLE LOGIC ZONE
Perform the following steps to enable or disable Logic Zones:
1.
In ENABLE/DISABLE tab, tap LOGIC ZONES to enable or disable a logic zone.
The Logic Zones screen opens with a list of programmed logic zones in the panel.
2.
Tap DETAILS to view operators applied, inputs and outputs associated with the logic zone.
3.
Tap ENABLE to enable a logic zone or tap DISABLE to disable a logic zone.
Fig. 26: Logic Zone Enable or Disable
When a logic zone is disabled, all its associated outputs get inhibited from activation.
In case, the output(s) are already activated by the logic zone, performing the logic zone disablement will deactivate all its associated output(s).
A logic zone which is disabled, is evaluated as logic 0, if it is part of/ cascaded as an input to other logic zones.
After the logic zone is re-enabled, all its associated output(s) return to the required state, as per the configured logic rule.