2.2 Testing Communications, Continued
Procedure, continued
Table 2 Testing Communications with Transmitter, Continued
Step Press Key Read Display or Action Description
5
TA ON.G
SFC WORK ING. . .
LIN AG NO.DP T
_
OR
DE X TM TA OG.RN
_
OR
TAG O
ORXT ONM ES
N.
NSRPE
Message exchange is taking place
Note that communications with
transmitter are blocked until [
ID] key
is pressed
Transmitter is in analog
transmission mode. “LIN” means
transmitter is set for linear output
instead of square root (SQRT). “DP”
means transmitter is differential
pressure type instead of gauge
pressure (GP) or absolute pressure
(AP). Last eight columns in bottom
row are blank when no tag number
has been assigned to this
transmitter. Go to Step 8.
Transmitter is in digital (DE)
transmission mode. Last eight
columns in bottom row are blank
when no tag number has been
assigned to this transmitter. Go to
Step 7.
Communication error messages are
cycled at two second intervals and
display returns to initial prompt. Go
to Step 6.
6
There is a communication problem,
check the
power and SFC connections - Is the
polarity correct; red to positive and
black to negative?
loop resistance - Is there a minimum
of 250 ohms resistance between the
SFC and the power supply?
power supply - Is power applied, is
there greater than 11 volts at the
transmitter, and are you within the
operating area on the curve in Figure
13?
Correct any wiring, resistance, or
power supply problems, and try
communicating again - Press [
ID]
key.
If you are still not getting the
correct display, note error
messages and refer to
Troubleshooting section in the
transmitter’s User’s Manual 34-ST-
25-14 for probable cause.
Continued on next page
8 ST 3000 Release 300 Installation Guide 2/05

Table of Contents

Other manuals for Honeywell ST 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ST 3000 and is the answer not in the manual?

Honeywell ST 3000 Specifications

General IconGeneral
ManufacturerHoneywell
CategoryTransmitter
Stability±0.01% of URL per year
Operating Temperature-40 to 85°C (-40 to 185°F)
Communication ProtocolHART
Housing MaterialAluminum or Stainless Steel
Enclosure RatingIP66/67, NEMA 4X
Measurement TypeGauge, Absolute, Differential
Output Signal4-20 mA, HART
Process Temperature-40 to 121°C (-40 to 250°F)
Hazardous Area ApprovalsFM, CSA, ATEX, IECEx
Process Connection1/2" NPT
Material316L Stainless Steel, Hastelloy C